Victron MultiPlus 12V 500VA-1200VA
The Victron MultiPlus replaces the previous MultiPlus Compact. It is a powerful pure sine wave inverter, an advanced battery charger with adaptive charging technology and a super-fast AC transfer switch in a single compact enclosure.
The full-bridge plus toroidal transformer topology has proven itself to be highly reliable for many years. The Victron MultiPlus is short-circuit resistant and protects against overheating, regardless of whether this is caused by overloading or a high ambient temperature. The Multi Control panel allows a maximum generator or shore power to be set. The Victron MultiPlus then takes other power consumers into account and uses only the remaining power for charging, so that the generator or shore connection does not become overloaded. Where peak power is often only needed briefly, the Victron MultiPlus ensures that insufficient shore or generator power is immediately compensated with power from the battery. When the load decreases, the reserve power is used to recharge the battery. Three-pin plug.
General specifications
| PowerControl / PowerAssist | No |
| Three-phase and parallel operation | No |
| Transfer switch | 16A |
| Programmable relay 1) | yes |
| Protections | • Short circuit output • Overload • Battery voltage too high • Battery voltage too low • Temperature too high • 230VAC on inverter output • Input voltage with too high ripple |
| General features | Operating temperature range: -40 to +65°C (fan cooling) Humidity (no condensation): max. 95% |
Inverter
| Input voltage range | 9.5-17V 19-33V 38-66V |
| Output | Output voltage: 230 VAC ±2% 2) Frequency: 50Hz ±0.1% 3) |
| Cont. output power at 25°C 3) | 500VA |
| Cont. output power at 25°C | 430W |
| Cont. output power at 40°C | 400W |
| Cont. output power at 65°C | 300W |
| Peak power | 900W |
| Max. efficiency | 90/91/92% |
| No-load power | 6/6/7W |
| No-load power in search mode | 2/2/3W |
Charger
| AC input | Input voltage range: 187-265VAC Input frequency: 45 –65Hz |
| Charging voltage bulk charge | 14.4 / 28.8 / 57.6 V |
| Charging voltage float charge | 13.8 / 27.6 / 55.2 V |
| Storage mode | 13.2 / 26.4 / 52.8 V |
| Charging current battery enclosure 4) | 20 / 10 / 6 A |
| Charging current starter battery | 1A (only for 12V and 24V models) |
| Battery temperature sensor | Yes |
Enclosure
| General features | Material and color: Steel/ABS (blue RAL 5012) Protection class: IP 21 |
| Battery connection | 16/10/10 mm2 |
| 230VAC connection | G-ST18i plug |
| Weight | 4.4kg |
| Dimensions (hxbxd) | 311x182x100 mm |
Standards
| Safety | NEN-EN-IEC 60335-1, NEN-EN-IEC 60335-2-29, NEN-EN 62109-1 |
| Emission/immunity | NEN-EN 55014-1 / NEN-EN 55014-2 / NEN-EN-IEC 61000-3-2 / NEN-EN-IEC 61000-3-3 NEN-EN-IEC 61000-6-1, NEN-EN-IEC 61000-6-2, NEN-EN-IEC 61000-6-3 |
| Road vehicles | ECE R10-4 |
1) Programmable relay that can be set to a:
general alarm, DC under-voltage or generator start/stop signal function
Nominal AC value: 230 V/4 A
Nominal DC value: 4 A to 35V DC, 1A to 60V DC
2) Can be set to 60 Hz and to 240 V
3) Non-linear load, crest factor 3:1
4) At 25°C ambient temperature